Celiera DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS Service Manual

Browse online or download Service Manual for Split-system air conditioners Celiera DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS. Celiera DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS Service manual User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 2 - CONTENTS

8 It protects the valves and prevents water from dripping. The unit has 3 mins delay between continuously ON/OFF operations. Outdoor unit

Page 3 - 1. Precaution

93. Dimension 3.1 Indoor Units Model W(mm) H(mm) D(mm) MS9A-09HRDN1-MP0W MS9A-9HRDN1-BQ0W 790 (31.10in) 265 (10.43in) 198 (7.80i

Page 4

LHModel MS9A-09HRDN1-MP0W MS9A-9HRDN1-BQ0W Model MS9A-9CRDN1-BS0W MS9A-9HRDN1-BS0W MS9A-12HRDN1-MP0W MS9A-12CRDN1-BS0W MS9A-12HRDN1-BS0W MS9A-12CRDN1

Page 5 - Ø CAUTION

Model MS9A-18HRDN1-MP0W MS9A-18CRDN1-MS0W MS9A-18HRDN1-MS0W MS9A-24HRDN1-MP0W MS9A-24CRDN1-MP0W Model MS9A-24HRDN1-MS0W 11 L(mm)

Page 6 - Ø Operational

123.2 Outdoor Units More than 30cmMore than 60cmMore than 70cmMore than 30cmMore than 60cm(Service spaceFence orobstacles Model

Page 7

13 4. Refrigerant Cycle Diagram For cooling only models: INDOOROUTDOORLIQUID SIDEGAS SIDEHEATEXCHANGE(EVAPORATOR)HEATEXCHANGE(CONDENSER)CO

Page 8 - 2. Function

14For heat pump models: INDOOROUTDOORLIQUID SIDEGAS SIDEHEATEXCHANGE(EVAPORATOR)HEATEXCHANGE(CONDENSER)COMPRESSOR2-WAY VALVE3-WAY VALVECHE

Page 9

155. Wiring Diagram 5.1 Indoor Units MS9A-09HRDN1-MP0W; MS9A-12HRDN1-MP0W; MS9A-12CRDN1-MS0W; MS9A-12HRDN1-MS0W MS9A-9CRDN1-BS0W; MS9A-9H

Page 10

16 MS9A-18HRDN1-MP0W;MS9A-18CRDN1-MS0W;MS9A-18HRDN1-MS0W; MS9A-24HRDN1-MP0W

Page 11 - 3. Dimension

17MS9A-9HRDN1-BQ0W MS9A-12HRDN1-BS0W(B)

Page 12

CONTENTS 1. Precaution ...

Page 13

18MS9A-24CRDN1-MP0W

Page 14 - 3.2 Outdoor Units

19MS9A-24HRDN1-MS0W

Page 15 - 4. Refrigerant Cycle Diagram

205.2 Outdoor Units MOC-09HDN1-MP0W;MOC-12HDN1-MP0W MOC-9CFN1-BS0W; MOC-9HRFN1-BS0W; MOC-12CFN1-BS0W; MOC-12HRFN1-BS0W

Page 16

21MOC-12CRDN1-MSOW MOC-12HRFN1-MS0W

Page 17 - 5. Wiring Diagram

22MOF-18HDN1-MP0W MOF-18CRFN1-MSOW

Page 18 - 16

23MOF-18HRFN1-MS0W MOG-24HDN1-MP0W

Page 19

24MOC-09HFN1-BQ0W, MOC-12HFN1-BS0W MOF-24HDN1-MP0W

Page 20 - MS9A-24CRDN1-MP0W

25MOG-24HDN1-MS0W MOF-24CDN1-MP0W

Page 21 - MS9A-24HRDN1-MS0W

266. Installation details 6.1 Wrench torque sheet for installation Outside diameter Torque Additional tightening torque mm inch N.cm

Page 22 - 5.2 Outdoor Units

276.2 Connecting the cables The power cord of connect should be selected according to the following specifications sheet. Rated current of

Page 23

1 1. Precaution 1.1 Safety Precaution n To prevent injury to the user or other people and property damage, the following instructions must be follo

Page 24

286.3 Pipe length and the elevation The pipe length and refrigerant amount: Model Connective pipe length Air purging method Additional a

Page 25 - MOG-24HDN1-MP0W

296.4 Installation for the first time Air and moisture in the refrigerant system have undesirable effects as below: Pressure in the syst

Page 26

30the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If the pressure can’t achieve -0.1Mpa

Page 27

31Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the 2-way valve approximately 45’ u

Page 28 - 6. Installation details

326).When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose from the 3-way valve’s service

Page 29 - 6.2 Connecting the cables

336).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low side), disconnect the charge hos

Page 30

345). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa. 6). Set the 3-way valve to the closed

Page 31

35Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the 2-way valve approximately 45’ u

Page 32

362. Refrigerant charging Procedure: 1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve Conne

Page 33

37Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.

Page 34

2condenser and evaporator. n For installation, always contact the dealer or an Authorized service center. There is risk of fire, electric

Page 35

387. Operation characteristics CAUTION: 1. If air conditioner is used outside of the above conditions, certain safety protection feature

Page 36

398. Electronic function 8.1 Abbreviation T1: Indoor room temperature T2: Coil temperature of evaporator T3: Coil temperature of

Page 37

40 DEFROST indication lamp (For cooling & heating models only): Lights up when the air conditioner starts defrosting automatically o

Page 38

418.3.6 Indoor fan delayed open function When the unit starts up, the louver will be active immediately and the indoor fan will open 10s l

Page 39 - 37

42 8.4.2 Cooling Mode 8.4.2.1 Compressor running rules: The operation frequency of compressor after starting submits to following rule. 4

Page 40 - 7. Operation characteristics

43Note: When T1-Ts keeps in the same temp. zone for 3 minutes, the compressor will run as the below rules: A~E: Increase the frequency to

Page 41 - 8. Electronic function

44auto. Auto fan in cooling mode acts as follow: 43HighLow1Medium1.5 8.4.2.4 Condenser high temperature T3 protection. ---55<T3<60 ,

Page 42 - 8.3 Main Protection

458.4.3 Heating Mode 8.4.3.1 Compressor running rules: The maximum operation frequency of the compressor after starting submits to the fol

Page 43

46+5.0+4.5+3.5+3.0+2.5+2.0+1.5+1.0HGHFEDCBA+0.5 While Temp. zone A B C D E F G Frequency F10 F9 F8 F7 F5 F3 F1 ∆T=0 as factory setting.

Page 44

47I3HEATI2HEATI1HEATOff DecreaseHoldResume Off: Compressor stops. Decrease: Decrease the running frequency to the lower level.

Page 45 - Decrease

3There is risk of explosion or fire. n If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the po

Page 46 - >=5

488.4.3.3 Indoor fan running rules: 4438373433SettingLowBreezeOff17 If the compressor stops caused by the room temperature rising, the ind

Page 47

49The units run with T3 3 for 80 minutes and T3 keeps lower than TCDI+2 for more than 3 minutes. While TCDI=6 . ----T

Page 48

50Defrosting action For 18k, 24k models: Model FD FD1 MS9A-18HRDN1-MS0W, 60 70 MS9A-24HRDN1-MS0W 90 100 MS9A-18HRDN1-MP0W MS9A-24

Page 49

51For other models: 8.4.3.5 Evaporator coil temperature protection ----T2> TEH2, the compressor running frequency decreases to the low

Page 50

52∆T 1 Cooling -1<∆T≤1 Fan-only ∆T≤-1 Heating Indoor fan will run at auto fan of the relevant mode. The louver operates same as in r

Page 51

53When the machine is off, pressing the touch button will carry the machine to forced auto mode. After this, pressing the button once agai

Page 52

54When heating, the setting temperature decreases 1 (be higher than 17 ) every one hour, 2 hours later the setting temperature stops ris

Page 53

559. Troubleshooting 9.1 Indoor Unit Error Display Display LED STATUS E0 EEPROM parameter error E1 Indoor / outdoor units communication

Page 54

569.2 Diagnosis and Solution 9.2.1 EEPROM parameter error diagnosis and solution Shut off the power supply and turn on it 5s later The pr

Page 55

579.2.2 Indoor unit and outdoor unit communication protection error diagnosis and solution Yes No No Change the indoor PCB Change the ou

Page 56

4n Keep level even when installing the product. It can avoid vibration of water leakage. n Do not install the product where the noise or

Page 57 - 9. Troubleshooting

589.2.3 Fan speed has been out of control diagnosis 9.2.4 Open or short circuit of temperature sensor diagnosis and solution Yes Repla

Page 58 - 9.2 Diagnosis and Solution

599.2.5 IGBT over-strong current protection diagnosis and solution 9.2.6 Over voltage or too low voltage protection diagnosis and solutio

Page 59

609.2.8 Inverter compressor drive error diagnosis and solution 9.2.9 Zero crossing detection error This is alarm signal when the main chi

Page 60

61Appendix: 10 11 12 13 14 15 16 F 48 50 52 54 56 58 60 17 18 19 20 21 22 23 F 62 64 66 68 70 72 74 24 25

Page 61

5damage. n Do not insert hands or other object through air inlet or outlet while the product is operated. There are sharp and moving part

Page 62

62. Function Model Names of Indoor/Outdoor Units DC Inverter Capacity Model Indoor units Outdoor units 9K MS9A-09HRDN1-MP0W MS9A-09HRDN

Page 63

7 The louver can be set at the desired position or swing up and down automatically The function is usually used in rainy days in springti

Comments to this Manuals

No comments